Cold & Hot Aisle Containment — Layouts, Doors and Fire Release
Containment systems that separate cold supply from hot return, with skylights, doors and fire-release mechanisms.
Aisle containment separates cold supply air from hot return air using a frame, roof panels and end doors. A 1,200 mm aisle, 2,000–2,200 mm frame height and 900 × 2,000 mm doors are typical. Good sealing can cut cooling energy by 10% to 20% and support 25–50 kW row cooling.
Last reviewed: 2026-11-07
Containment is the lowest-cost way to improve cooling efficiency in an existing room. It does not add cooling capacity; it stops the cooling system from wasting capacity on mixed air.
Skylights can open on fire alarm; doors can include access control. The frame is independent of cabinet load-bearing.
Best for
- Data centers and computing halls
- Existing rooms with hot spots
- High-density server rows
Key specifications
Cold vs hot aisle containment
| Feature | Cold aisle | Hot aisle |
|---|---|---|
| Enclosed space | Cold supply | Hot return |
| Retrofit | Easier | More demanding |
| Typical use | Existing rooms | New high-density halls |
| Fire strategy | Skylights release | Heat/smoke exhaust |
How to choose
Survey the row
Check heights, depths, aisle width, ceiling and fire interfaces.
Choose cold or hot
Cold aisle for retrofits; hot aisle for new high-density halls.
Plan fire release
Link skylights to the alarm and test with the fire system.
Cold aisle vs hot aisle containment
Cold aisle containment encloses the cold supply aisle and leaves the hot aisle open to the room. It is common in retrofit projects because the cold aisle is usually the front of the cabinets and easier to enclose.
Hot aisle containment encloses the hot return aisle and leaves the cold aisle open. It can be better for high-density rows and for rooms where the ceiling is used as the hot return plenum. Both types need sealed cable openings and blanking panels.
Sizing the aisle and frame
A 1,200 mm aisle is the standard for data centers. It allows two people to pass and gives room for door swing and equipment installation. The frame height is 2,000 mm to 2,200 mm, matching the cabinet row and the ceiling grid.
Doors are typically 900 mm wide and 2,000 mm high, in sliding or swing versions. Sliding doors save space in tight rooms; swing doors give a wider opening. The frame is aluminum with adjustable feet and does not load the cabinets.
Sealing, airflow and commissioning
The target is to keep leakage below about 5% of the supply airflow. Seal cable openings, blank unused U positions and close gaps at the top and bottom of the row. A pressure difference of 5 Pa to 15 Pa between the cold aisle and the room is a useful check.
Measure the intake temperature at the top, middle and bottom of several cabinets. With good sealing, the variation along the row should be within 1 °C to 2 °C. That allows a higher supply air temperature and better chiller efficiency.
Options and delivery
Options include glass or polycarbonate roof panels, drop-away skylights for fire suppression, LED lighting, brush seals and blanking panels. Typical lead time is 20 to 30 working days after drawing approval.
Aisle containment reference
| Item | Typical value | Notes |
|---|---|---|
| Aisle width | 1,200 mm | Two-person access |
| Frame height | 2,000–2,200 mm | Match cabinet row |
| Door size | 900 × 2,000 mm | Sliding or swing |
| Roof panel | Glass / PC | 70–80% light |
| Leakage target | <5% | Commissioning |
| Intake variation | 1–2 °C | Along row |
| Cooling | 25–50 kW | Row units |
| Lead time | 20–30 days | After drawing |
Cold vs hot aisle
| Item | Cold aisle | Hot aisle |
|---|---|---|
| Enclosed | Cold supply | Hot return |
| Retrofit | Easier | Harder |
| High density | Good | Better |
| Ceiling plenum | Not required | Often used |
| Door location | Front of row | Rear of row |
| Common use | Most projects | High-density rows |
Containment options
| Option | Choices | Use |
|---|---|---|
| Roof | Glass / PC / solid | Light and fire |
| Skylight | Fixed / drop-away | Fire suppression |
| Door | Sliding / swing | Space |
| Seals | Brush / magnetic | Cable gaps |
| Lighting | LED strip | Service |
| Control | Door sensor | Monitoring |
Frequently asked questions
08 Q&A Does containment replace air conditioning?
Can containment be retrofitted?
What happens to skylights on fire alarm?
Which is better, cold aisle or hot aisle containment?
How wide should a contained aisle be?
How much energy does containment save?
Can containment be retrofitted to existing cabinets?
Does containment work with a raised floor?